AL XZ1 (S)

AL XZ1 (S)

Rigid aluminum LSZH cable, suitable for power transmission.

Rated voltage:  U0/U 0,6/1 kV
Standards: EN 50288-7, IEC 60502-1
Cables with aluminum conductors, cross-linked polyethylene insulation and halógena-free polyolefin sheath.

According to standards  HD-603-5X

Application

Cable for fixed installations in low voltage public distribution networks. Suitable for indoor, outdoor and buried installations.

Application

Cable for fixed installations in low voltage public distribution networks. Suitable for indoor, outdoor and buried installations.

      Conductor
      Aluminium, class 2
      EN 60228 - IEC 60228
      Insulation
      Cross-linked Polyethylene (XLPE)
      UNE HD 603-1
      Core Identification
      Colorless
       
      Outer sheath
      Low Smoke Zero Halogen (LSZH) polyolefin type DMO-1
      HD 603-1
      Colour
      Black
      RAL 9005
      Rated voltage Uo/U 0,6/1 kV
      Test voltage 3500 V C.A.
      Minimum conductor temp. -15ºC
      Maximum conductor temp. 90ºC
      Maximum short-circuit temperature 250ºC (maximum 5 seconds)
      Limit bend radius 15 x outer diameter
      CPR Construction Eca according to EN 50288-7
      UV resistant Ok according to UNE-HD 603-1
      Flame non-propagation Ok according to IEC 60332-1-2
      LSHF (Low Smoke Halogen Free) Ok according to IEC 60754-1, EN 60754-1
      Low smoke emisión Ok according to UNE-HD 603-1