Rated voltage: 0,6/1 kV
Standards: UNE 21123
Flexible conductor cable, XLPE insulation, LSZH sheath (halogen-free), fire-resistant and low smoke emission.
Used in fixed installations, especially in public buildings, industrial installations, and tunnels, where high fire safety and low emission of smoke and toxic gases are required.
Used in fixed installations, especially in public buildings, industrial installations, and tunnels, where high fire safety and low emission of smoke and toxic gases are required.
Conductor Flexible electrolytic copper conductor class 5 |
EN 60228, IEC 60228 |
Insulation Cross-linked polyethylene DIX-3 |
UNE 21123-4 |
Core identification |
HD308 6c o more conductors :Black numbered + Green/yellow |
Outer sheath Low-smoke Zero halogen cross-linked polyolefin ST8 |
UNE EN 21123-4 |
Color Green, others colors white or black |
Rated voltage | 0,6/1 kV |
Test voltaje | 3.500 V C.A. |
Maximum conductor temperatura | 90ºC |
CPR Construction | Cca-s1b, d1, a1 according to UNE-EN 50575 |
Flame non-propagation | Ok according to IEC 60332-1-2 |
Fire non-propagation | Ok according to EN 50399 |
LSHF (Low Smoke Halogen Free) | Ok according to IEC 60754-1 |
Low corrosive gas | Ok according to IEC 61034-2 |